%0 Journal Article %T DGA Interpretation of Oil Filled Transformer Condition Diagnosis %A Ali Saeed Alghamdi %A Nor Asiah Muhamad %A Abubakar A. Suleiman %J Transactions on Electrical and Electronic Materials %D 2012 %I Korean Institute of Electrical and Electronic Material Engineers (KIEEME) %X DGA is one of the most recent techniques developed to diagnose the fault condition on oil filled insulationtransformers. There are more than 6 known different methods of DGA fault interpretation technique and so thereis the likelihood that they may vary in their interpretations. A series of combined interpretation methods that candetermine the power transformer condition faults in one assessment is therefore needed. This paper presents acomputer program- based system developed to combine four DGA assessment techniques; Rogers Ratio Method, IECBasic Ratio Method, Duval Triangle method and Key Gas Method. An easy to use Graphic User Interface was designedto give a visual display of the four techniques. The result shows that this assessment method can increase the accuracyof DGA methods by up to 20% and the no prediction result had been reduced down to 0%. %K Dissolved gas analysis (DGA) %K Oil filled transformer %K Fault analysis %U http://dx.doi.org/10.4313/TEEM.2012.13.5.229