%0 Journal Article %T Assessment of Indoor and Outdoor Noise Pollution at a University Hospital Based on Acoustic Measurements and Noise Mapping %A Paulo Henrique Trombetta Zannin %A Fernanda Ferraz %J Open Journal of Acoustics %P 71-85 %@ 2162-5794 %D 2016 %I Scientific Research Publishing %R 10.4236/oja.2016.64006 %X This paper describes an analysis of the sound pressure levels at the exterior façade and inside the Hospital de Cl¨ªnicas of the Federal University of Paran¨¢. Measurements were taken at a total of 45 points, 24 at the exterior facade and 21 points inside the hospital on all the floors of the main building and in the maternity building. These 45 measurements were used to calculate the acoustic map of the hospital, which is located on General Carneiro Street, in the city of Curitiba, state of Paran¨¢, Brazil. A comparison of the measured outdoor sound pressure levels against those established by Curitiba Municipal Law No. 10625 revealed that they all exceeded the daytime limit of 55 dB(A) permitted for areas around hospitals. The indoor sound pressure measurements and the noise levels for acoustic comfort established by the Brazilian technical standard ABNT NBR 10152 were compared, indicating that all the measured points, including those in the neonatal intensive care unit, exceeded the established limit of 35 dB(A) to 45 dB(A). %K Noise Pollution %K University Hospital of The Federal University of Paraná %K Sound Measurements %K Sound Pressure Levels %K Noise Mapping %U http://www.scirp.org/journal/PaperInformation.aspx?PaperID=72974