长沙地区某联通机房热管空调改造的节能分析
|
Abstract:
在2030“碳达峰”及2060年的“碳中和”背景下,各行业纷纷出台各项标准与应用低碳技术以响应国家政策。而IDC (Information Data Center)机房其能耗呈井喷式增长,节能降耗迫在眉睫。针对该形式,日前省发改委出台了“数据中心及5G基站”低碳行动方案。热管自然冷却是降低这一能耗的有效方法之一。本文针对长沙地区某联通机房热管空调改造项目进行建模分析,并以实测值验证。结果表明,该系统的节能率约为38%。这是一项值得在全国范围推广的技术。
Under the background of “carbon peak” in 2030 and “carbon neutralization” in 2060, the form of energy conservation in various industries is severe. The energy consumption of IDC (Information Data Center) room is increasing in a blowout mode, so it is urgent to save energy and reduce consumption. In view of this form, the provincial development and Reform Commission recently issued a low-carbon action plan of “data center and 5G base station”. Natural cooling of a heat pipe is one of the effective methods to reduce this energy consumption. This paper analyzes the modeling of a heat pipe air conditioning transformation project in a Unicom room in Changsha, and verifies it with the measured values. The results show that the energy saving rate of the system is about 38%. It is a technology worthy of nationwide promotion.
[1] | 陈飞虎, 周新力, 廖曙光. 重力热管型双循环空调在夏热冬冷地区应用探讨[J]. 暖通空调, 2022, 51(1): 152-155 |
[2] | 张文佺, 张素芳, 王晓烨, 乔军晶, 张晶, 孔维鉴. 点亮绿色云端: 中国数据中心能耗与可再生能源使用潜力研究[R]. 保定: 国际环保组织绿色和平与华北电力大学, 2020. |
[3] | 刘丽辉, 莫雅菁, 孙小琴, 李杰, 李传常, 谢宝姗. 纳米增强型复合相变材料的传热特性[J]. 储能科学与技术, 2020, 9(4): 1105-1112 |
[4] | 王铁军, 赵丽, 吕继祥, 等. 热管复合式制冷机组的研发与应用[J]. 制冷学报, 2016, 37(4): 65-69. |
[5] | 陈飞虎, 廖曙光. 某电信机房节能改造全年能效的热力学分析[J]. 建筑热能通风空调, 2021, 40(10): 55-58 |
[6] | 陈飞虎, 廖曙光, 龚光彩, 等. 数据中心热管空调系统仿真研究——基于热力学模拟软件CYCLEPAD [J]. 洁净与空调技术, 2020(4): 27-33. |
[7] | 王子彪, 熊伟, 刘艺唯, 等. 热管-蓄冷空调系统在数据中心的节能应用方案研究[J]. 制冷与空调, 2015, 15(9): 71-74+80. |
[8] | 吕继祥, 王铁军, 赵丽, 等. 基于自然冷却技术应用的数据中心空调节能分析[J]. 制冷学报, 2016, 37(3): 113-118. |
[9] | 钱晓栋, 李震, 李志信. 数据机房热管空调系统的实验研究[J]. 工程热物理学报, 2012, 33(7): 1217-1220. |
[10] | 刘书浩, 张海涛, 郭佳哲. 数据中心热管背板空调应用实测研究——系统不平衡运行分析[J]. 制冷与空调, 2015, 15(3): 22-25+12. |