环网柜可分离连接器绝缘故障模拟及典型气体释放规律研究
Research on Insulation Failure Simulation and Typical Gas Release Law of Detachable Connectors in Ring Cabinet

DOI: 10.12677/JEE.2023.112005, PP. 37-45

Keywords: 可分离连接器,绝缘故障模拟,气体成份分析
Detachable Connector
, Insulation Fault Simulation, Gas Composition Analysis

Full-Text   Cite this paper   Add to My Lib

Abstract:

为更好的实现气体组分分析法在环网柜绝缘状态预测评估这一领域的应用,本文对环网柜可分离连接器绝缘故障模拟及典型气体释放规律进行研究。实验对环网柜可分离连接器典型绝缘故障进行模拟,包括可分离连接器装配不到位、套管与可分离连接器之间有金属丝、套管表面有凹陷、可分离连接器内表面有凹陷,同时选取非甲烷总烃、氢气、一氧化碳作为监测目标物。得出如下结论:环网柜可分离连接器典型绝缘故障模拟过程中会生成氢气、一氧化碳、非甲烷总烃气体;氢气、一氧化碳、非甲烷总烃气体浓度大小以及变化规律存在差异;试验箱内部位于可分离连接器上方的传感器氢气数值远大于下方传感器数值。试验箱内部气体浓度位于可分离连接器下部的一氧化碳传感器数值大于上部传感器数值;在可分离连接器装配不到位、套管表面有凹陷、可分离连接器内表面有凹陷绝缘故障模拟过程中,试验箱内部气体浓度位于可分离连接器下部的非甲烷总烃传感器数值大于上部传感器数值,在套管与可分离连接器之间有金属丝绝缘故障模拟过程中,试验箱内部气体浓度位于可分离连接器下部的非甲烷总烃传感器数值小于上部传感器数值。
In order to better realize the application of gas component analysis method in the prediction and evaluation of ring cabinet insulation state, this paper studies the insulation fault simulation and typical gas release law of the detachable connector of ring cabinet. Typical insulation failures of detachable connectors in ring cabinet were simulated in the experiment, including the assembly of detachable connectors was not in place, there were metal wires between the sleeve and the detachable connector, there were dents on the surface of the sleeve, and there were dents on the inner surface of the detachable connector. At the same time, non-methane total hydrocarbons, hydrogen and carbon monoxide were selected as monitoring targets. The following conclusions are drawn: Hydrogen, carbon monoxide and non-methane total hydrocarbon gases are generated during the typical insulation failure simulation of the detachable connector of the ring cabinet. There are differences in the concentration of hydrogen, carbon monoxide and non-methane hydrocarbon gases. The hydrogen value of the sensor above the detachable connector inside the test chamber is much greater than that of the sensor below it. The carbon monoxide sensor with the gas concentration in the test chamber located at the lower part of the separable connector is greater than the upper part of the sensor. In the insulation fault simulation process where the assembly of the detachable connector is not in place, the casing surface is concave, and the inner surface of the detachable connector is concave, the value of the non-methane total hydrocarbon sensor whose gas concentration in the test chamber is located at the lower part of the detachable connector is greater than the value of the upper sensor. In the insulation fault simulation process where there is wire between the casing and the detachable connector, the non-methane total hydrocarbon sensor with the gas concentration in the test chamber at the lower part of the separable connector is smaller than that at the upper part.

References

[1]  陈宇. 配电网中箱变及环网柜技术应用[J]. 中国科技纵横, 2012 (21): 146.
[2]  金琪, 李烽, 顾临峰, 等. 新型智能化环网柜的设计及实现[J]. 华东电力, 2014, 42 (7): 1373-1376.
[3]  苗爱敏, 邹勋, 李鹏, 等. 环网柜故障监测方法综述[J]. 工业工程, 2017, 20(36): 64-70.
[4]  黄晨奕, 李红梅, 黄佳宁, 等. 10 kV屏蔽型可分离连接器应力锥典型故障分析[J]. 高电压技术, 2022, 12(58): 69-74.
[5]  方春华, 潘明龙, 易满成, 等. 环网柜电缆室电缆过长对套管受力分析[J]. 高压电器, 2018, 54(1): 23-28.
[6]  潘明龙, 方春华, 易满成, 等. 环网柜电缆室电缆屈曲对套管受力的影响规律[J]. 高压电器, 2019, 55(5): 94-99.
[7]  潘长明, 刘刚, 熊炬, 等. 高压开关柜绝缘事故的分析及防范措施[J]. 高压电器, 2011, 47(7): 90-93.
[8]  周凤争, 孟庆霖, 朱晓辉, 等. 10 kV电缆附件典型缺陷仿真与绝缘故障分析[J]. 绝缘材料, 2011, 44(4): 67-69.
[9]  邱昌容, 王乃庆, 等. 电工设备局部放电及其测试技术[M]. 北京: 机械工业出版社, 1994.
[10]  彭超, 雷清泉. 局部放电超高频信号时频特性与传播距离的关系[J]. 高电压技术, 2013, 39(2): 348-353.
[11]  牛勃, 马飞越, 丁培, 等. 臭氧浓度检测技术在开关柜局部放电检测中的应用[J]. 绝缘材料, 2018, 51(8): 69-74.
[12]  张振宇, 李永祥, 杨罡, 等. 开关柜故障衍生气体实验模拟及分析[J]. 武汉大学学报, 2021, 8(54): 769-776.
[13]  吴佳玮, 韩若愚, 周海滨, 等. 大电流气体火花开关聚四氟乙烯绝缘子绝缘劣化产物分析[J]. 电工技术学报, 2018, 2(33): 459-466.
[14]  唐传佳, 刘志存, 陈立新, 等. 基于臭氧检测的高压开关柜初始放电预警技术[J]. 上海电气技术, 2018, 11(3): 50-52.