R290用焓差实验室制冷剂泄漏模拟分析
Laboratory Refrigerant Leak Simulation Analysis with Enthalpy Difference for R290

DOI: 10.12677/MOS.2024.131040, PP. 421-429

Keywords: R290,泄漏,CFD,焓差实验室,浓度场
R290
, Leak, CFD, Enthalpy Difference Laboratory, Concentration Field

Full-Text   Cite this paper   Add to My Lib

Abstract:

R290是一种很有前途的空调替代制冷剂,为了促进R290在空调中的安全应用,本文以某单位建好的R290用焓差实验室为研究对象,建立了在有限空间内存在室内自循环的制冷剂泄漏和扩散的数学模型,对以使用R290为制冷剂的被测制冷设备(热泵)在发生泄漏的情况下,用CFD对泄漏后的试验房间进行模拟计算,分析探讨R290泄露到有限外部空间的爆炸风险。本文假设泄漏孔为圆形泄漏孔,泄漏孔直径为4 mm,泄漏量1.3 kg,泄漏时间为240 s,整个过程匀速泄漏,发现在整个过程中,除开在泄漏时间(240 s)内的泄漏口附近之外,整个泄漏过程都不存在R290燃爆的浓度区间。
R290 is a promising alternative refrigerant for air conditioning. In order to promote the safe appli-cation of R290 in air conditioning, this paper takes the R290 enthalpy difference laboratory built by a certain unit as the research object, and establishes a mathematical model for the leakage and dif-fusion of indoor self-circulating refrigerant in a limited space. In the case of leakage of the tested re-frigeration equipment (heat pump) using R290 as refrigerant, CFD is used to simulate the test room after leakage, and the explosion risk of R290 leaking into the limited outer space is analyzed and discussed. In this paper, it is assumed that the leakage hole is a circular leak hole, the diameter of the leak hole is 4 mm, the leakage amount is 1.3 kg, and the leakage time is 240 s, and the leakage rate is uniform throughout the whole process. It is found that there is no concentration range of R290 explosion in the whole process except near the leakage port within the leakage time (240 s).

References

[1]  全国冷冻空调设备标准化技术委员会. GB/T 7778-2017制冷剂编号方法和安全性分类[S]. 北京: 中国标准出版社, 2020.
[2]  Colbourne, D., Pitarch Mocholi, M., Munzinger, P., Oppelt, D., Paetzold, B. and Vince, I. (2021) Leak Hole Sizes from Refrigeration, Air Conditioning and Heat Pump Systems. International Journal of Refrigeration, 131, 559-567.
https://doi.org/10.1016/j.ijrefrig.2021.07.003
[3]  Li, Y., Yang, J., Wu, X., et al. (2023) Explosion Risk Analysis of R290 Leakage into a Limited External Space. Applied Thermal Engineering, 225, 120122.
https://doi.org/10.1016/j.applthermaleng.2023.120122
[4]  丁家琦. R290空气源冷热水热泵机组泄漏安全性研究[D]: [硕士学位论文]. 武汉: 华中科技大学, 2019.
[5]  海腾蛟. 家用空调可燃制冷剂泄漏危险性模拟[D]: [硕士学位论文]. 武汉: 华中科技大学, 2014.
[6]  Li, T. (2014) Indoor Leakage Test for Safety of R-290 Split Type Room Air Conditioner. International Journal of Refrigeration, 40, 380-389.
https://doi.org/10.1016/j.ijrefrig.2013.11.023
[7]  全国冷冻空调设备标准化技术委员会. GB/T 21362-2023商业或工业用及类似用途的热泵热水机[S]. 北京: 中国标准出版社, 2023.
[8]  孙秉才, 冉冉, 顾晓敏, 等. LPG低温储罐泄漏扩散数值模拟及影响因素分析[J]. 工业安全与环保, 2022, 48(9): 26-30.
[9]  李盼. 机械回转反吹袋滤器内温度场和流场数值模拟[D]: [硕士学位论文]. 秦皇岛: 东北大学, 2017.