Mitigation of Transients in Capacitor Coupled Substations Using Traditional RLC Filter Techniques

DOI: 10.4236/jpee.2024.125003, PP. 60-75

Keywords: Capacitor Coupled Substation, System Modeling, Ferroresonance, RLC filters, Power Electronics, Transients, Capacitor Voltage Transformers, Transmission Lines

Full-Text   Cite this paper   Add to My Lib

Abstract:

This article presents an extensive examination and modeling of Capacitor Coupled Substations (CCS), noting some of their inherent constraints. The underlying implementation of a CCS is to supply electricity directly from high-voltage (HV) transmission lines to low-voltage (LV) consumers through coupling capacitors and is said to be cost-effective as compared to conventional distribution networks. However, the functionality of such substations is susceptible to various transient phenomena, including ferroresonance and overvoltage occurrences. To address these challenges, the study uses simulations to evaluate the effectiveness of conventional resistor-inductor-capacitor (RLC) filter in mitigating hazardous overvoltage resulting from transients. The proposed methodology entails using standard RLC filter to suppress transients and its associated overvoltage risks. Through a series of MATLAB/Simulink simulations, the research emphasizes the practical effectiveness of this technique. The study examines the impact of transients under varied operational scenarios, including no-load switching conditions, temporary short-circuits, and load on/off events. The primary aim of the article is to assess the viability of using an established technology to manage system instabilities upon the energization of a CCS under no-load circumstances or in case of a short-circuit fault occurring on the primary side of the CCS distribution transformer. The findings underscore the effectiveness of conventional RLC filters in suppressing transients induced by the CCS no-load switching.

References

[1]  Abdel-Hamed, A.M., El-Shafhy, M.M. and Badran, E.A. (2022) High Ohmic Reactor as a Shunt Limiter (HOR-SL) Method for Ferroresonance Elimination in the Distribution System. IEEE Access, 10, 134217-134229.
https://doi.org/10.1109/ACCESS.2022.3231190
[2]  Abdel-Hamed, A.M., El-Shafhy, M.M. and Badran, E.A. (2023) Investigating Ferroresonance in the Distribution Zone. 2022 23rd International Middle East Power Systems Conference (MEPCON), Cairo, 13-15 December 2022, 1-8.
https://doi.org/10.1109/MEPCON55441.2022.10021717
[3]  Akpan, U., Essien, M. and Isihak, S. (2013) The Impact of Rural Electrification on Rural Micro-Enterprises in Niger Delta, Nigeria. Energy for Sustainable Development, 17, 504-509.
https://doi.org/10.1016/j.esd.2013.06.004
[4]  Alghaythi, M.L., Irudayaraj, G.C., Ramu, S.K., Govindaraj, P. and Vairavasundaram, I. (2023) Mathematical Modeling and Analysis of Capacitor Voltage Balancing for Power Converters with Fewer Switches. Sustainability, 15, Article 10698.
https://doi.org/10.3390/su151310698
[5]  Aminifar, F., Abedini, M., Amraee, T., Jafarian, P., Samimi, M.H. and Shahidehpour, M. (2022) A Review of Power System Protection and Asset Management with Machine Learning Techniques. Energy Systems, 13, 855-892.
https://doi.org/10.1007/s12667-021-00448-6
[6]  EL-Shafhy, M.M., Abdel-Hamed, A.M. and Badran, E.A. (2022) Ferroresonance in Distribution Systems—State of the Art. Przeglad Elektrotechniczny, 98, 1.
https://doi.org/10.15199/48.2022.11.01
[7]  Fathi, S.H. and Abbasi, A. (2018) New Technique for Elimination of Ferroresonant Oscillations in Series Capacitor of Power System. Asian Journal of Scientific Research, 11, 203-221.
https://doi.org/10.3923/ajsr.2018.203.221
[8]  Hepziba, R.J., Balaji, G., Muralikrishma, R. and Rathinavel, S. (2024) A Case Study on Transformer Ferroresonance for Subsea Cable Connected 230kV Substations Using PSCAD. Electric Power Systems Research, 230, Article ID: 110192.
https://doi.org/10.1016/j.epsr.2024.110192
[9]  Kalair, A., Abas, N., Kalair, A., Saleem, Z. and Khan, N. (2017) Review of Harmonic Analysis, Modeling and Mitigation Techniques. Renewable and Sustainable Energy Reviews, 78, 1152-1187.
https://doi.org/10.1016/j.rser.2017.04.121
[10]  Kraszewski, W., Syrek, P. and Mitoraj, M. (2022) Methods of Ferroresonance Mitigation in Voltage Transformers in 30kV Power Supply Network. Energies, 15, Article 9516.
https://doi.org/10.3390/en15249516
[11]  Lin, T.C., Wang, H.H. and Liu, C.H. (2021) Fault Location for Three-Ended Ring-Topology Power System Using Minimum GPS-Based Measurements and CVT/CT Sensing. IEEE Sensors Journal, 21, 22019-22031.
https://doi.org/10.1109/JSEN.2021.3100772
[12]  Martinez, E., Antonova, G. and Olguin, M. (2013) Ferroresonance Phenomenon in CFE, Its Origin and Effects. 2013 66th Annual Conference for Protective Relay Engineers, Texas, 8-11 April 2013, 450-466.
https://doi.org/10.1109/CPRE.2013.6822057
[13]  Meng, Z., Li, H., Zhang, C., Chen, M. and Chen, Q. (2019) Research on the Reliability of Capacitor Voltage Transformers Calibration Results. Measurement, 146, 770-779.
https://doi.org/10.1016/j.measurement.2019.07.011
[14]  Navaei, M., Abdoos, A.A. and Shahabi, M. (2018) A New Control Unit for Electronic Ferroresonance Suppression Circuit in Capacitor Voltage Transformers. International Journal of Electrical Power & Energy Systems, 99, 281-289.
https://doi.org/10.1016/j.ijepes.2018.01.021
[15]  Nene, S.W., Abe, B.T. and Nnachi, A.F. (2023) Modeling and Simulation of a Transmission Line Response to a 400 KV/400V Capacitor Coupled Substation. Journal of Power and Energy Engineering, 11, 1-14.
https://doi.org/10.4236/jpee.2023.1112001
[16]  Nilsson, S.L., Lima, M. and Young, D.J. (2020) AC Network Control Using Conventional Means. In: Andersen, B. and Nilsson, S., Eds., Flexible AC Transmission Systems, Springer, Cham, 51-89.
https://doi.org/10.1007/978-3-030-35386-5_3
[17]  Nogay, H. S. (2023) Forecasting of Voltage Disturbances at the Beginning of Ferroresonance Phenomena in Power Systems Using by a New Approach of Long-Short Term Memory (LSTM). Journal of Engineering Research, 11, 297-306.
[18]  Olanrewaju, E. and Olanrewaju, O. (2020) Rural Electrification and Profitability among Rural Women-Owned Microenterprises in Nigeria. International Journal of Economics, 8, 1-11.
https://doi.org/10.34293/economics.v8i4.3381
[19]  Pinheiro, P.H., Vidal, M.L., Rocha, F.F. and Fortes, B.W. (2020) Ferroresonance Evaluation on Capacitor Voltage Transformers. Electrical Engineering, 102, 1775-1783.
https://doi.org/10.1007/s00202-020-00992-x
[20]  Pinheiro, P.H., Vidal, M.L., Rocha, F.F., Franca, B.W. and Fortes, M.Z. (2020) Ferroresonance Evaluation on Capacitor Voltage Transformers. Electrical Engineering, 102, 1775-1783.
https://doi.org/10.1007/s00202-020-00992-x
[21]  Salihi, J.T. (1960) Theory of Ferroresonance. Transactions of the American Institute of Electrical Engineers, Part I: Communication and Electronics, 87, 755-763.
https://doi.org/10.1109/TCE.1960.6368465
[22]  Sanaye-Pasand, M. and Aghazadeh, R. (2003) Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronics Devices. International Conference on Power Systems Transients, New Orleans, 28 September-2 October 2003, 1-5.
[23]  Saulo, M.J. (2014) Penetration Level of Un-Conventional Rural Electrification Technologies on Power Networks. Ph.D Thesis, University of Cape Town, Cape Town.
[24]  Saulo, M.J. and Gaunt, C.T. (2015) The Impact of Capacitor Coupled Sub-Station in Rural Electrification of Sub-Saharan Africa. International Journal of Energy and Power Engineering, 4, 12-29.